What is the reason for the soft water hardness of boiler softening water equipment exceeding the standard?
Time:
2020-12-04 09:00
Source:
Users of boiler softening water equipment often have such questions: the system is very normal, and other indicators are also normal, but the hardness of the effluent is too high. I don’t know why?
1. The O-ring at the junction of the central pipe and the fully automatic softening control valve does not form a seal. At this time, it should be checked:
(1) Whether the length of the central tube is sufficient and whether the outer diameter meets the requirements.
(2) Did you forget to install the O-ring?
(3) Whether the O-ring seal is damaged.
(4) Whether the central tube is damaged or cracked.
2. The ratio of the raw water hardness index value to the height of the ion exchange resin layer is too large, and the water hardness of the primary sodium ion exchanger is required to be <8mmol/L.
3. The demineralized water runs too fast. It is strictly forbidden to work at the maximum flow rate allowed by the equipment for a long time. Note: GB/T18300 stipulates that the operating flow rate of the downstream regeneration fixed bed is 20-30m/h, and the upper limit is the instantaneous maximum value. It is strictly forbidden to work at this flow rate for a long time.
4. There is a large amount of gas in the resin tank, which may come from the air in the water supply, or the air check valve is not closed tightly during the slow cleaning process.
5. Large grain industrial soft water salt is not used.
6. The internal leakage of the fully automatic softened water control valve is hard: when the internal leakage of the general control valve is hard, the softened water outlet and the waste water outlet often come out at the same time.
The above is the solution to the water hardness of the boiler softening water equipment that has been sorted out by the editor of Yilida water treatment manufacturer. I hope it will be helpful to everyone.
Related news
The main factors for choosing a manufacturer of micro-bubble exhaust and decontamination devices?
The microbubble decontamination device can create a static area in the screw cleaner, so that all the large and small particles have time to settle to the bottom of the equipment and collect into the sediment chamber. With the globalization and intensification of market competition, the life cycle of products is getting shorter and shorter, and the emphasis on quality and delivery reliability increases the complexity and scope of supplier selection. So, let's learn about the manufacturer selection criteria below!
How to ensure better use of automatic softened water equipment
To get the best out of a fully automatic water softener, regular maintenance and immediate repairs are needed to make it last longer. In order to ensure the use effect of the fully automatic softened water equipment, daily maintenance must be done well.
Users of boiler softening water equipment often have such questions: the system is normal, and other indicators are also normal, but the hardness of the effluent is high. I don’t know why?
Parameter calculation method of constant pressure water supply device in HVAC system
According to the different constant pressure forms of heating and air-conditioning water systems, it can be divided into three constant pressure modes: constant pressure of expansion tank, constant pressure of air pressure tank and constant pressure of variable frequency make-up pump.